COMPARISON · MULTIMETERS
Fluke 1587 FC vs Fluke 287: Which Is Better for Electrical Diagnostics?
In this Fluke 1587 FC vs 287 comparison, the deciding question is whether your faults are found with the power on or with it off. The 1587 FC is the one to buy when you need to prove motor windings and cables are sound: it applies 50 to 1000 V and reads insulation up to 2 GΩ. The 287 is the one to buy when you need to watch a running circuit misbehave: it records for hours at 50,000 counts and measures from 0.01 µA up to 10 A. Both carry the same CAT IV 600V / CAT III 1000V rating, and we have not hands-on tested either.
By the OhmSavvy Research Team ·
Disclosure: OhmSavvy earns a commission from qualifying Amazon purchases made through these links, at no extra cost to you. How we're funded.

Fluke 1587 FC
4.6★★★★★A True RMS multimeter and 50–1000 V insulation tester in one, with PI/DAR tests and Fluke Connect logging to your phone.

Fluke 287
4.6★★★★★Fluke's electronics logging meter: 50,000 counts, 0.01 µA resolution and graphs on the meter, without the 289's industrial extras.
Specs side by side
| Fluke 1587 FC | Fluke 287 | |
|---|---|---|
| Rating | 4.6★★★★★ | 4.6★★★★★ |
| Accuracy | True RMS, ±(0.09% + 2) DC V | True RMS, 0.025% basic DC V |
| Safety rating | CAT IV 600V / CAT III 1000V | CAT IV 600V / CAT III 1000V |
| Auto-ranging | Yes (manual override) | Yes (manual override) |
| Best for | Motor, cable and insulation testing | Electronics design, µA and logging |
| Display | 6,000 counts | 50,000 counts with graphics |
| Insulation test | 50, 100, 250, 500, 1000 V; to 2 GΩ | None |
| DC volts accuracy (best) | ±(0.09% + 2) | ±(0.025% + 2) |
| AC volts accuracy | ±(1% + 3) at 50–60 Hz | ±(0.3% + 25) at 45–65 Hz |
| Low-pass filter | Yes | No (289 only) |
| Current | 60 mA and 400 mA ranges only | 0.01 µA resolution up to 10 A (20 A for 30 s) |
| Resistance (meter) | 0.1 Ω to 50 MΩ | 0.01 Ω to 500 MΩ |
| Capacitance | To 9,999 µF | 1 nF to 100 mF |
| Frequency | To 99.99 kHz | 0.5 Hz to 999.99 kHz, plus duty cycle |
| Temperature | -40 to 537 °C, K-type included | -200 to 1350 °C (probe excluded) |
| Recording | To the Fluke Connect app | Up to 10,000 intervals in the meter |
| Data link | 2.4 GHz radio to phone or tablet | IR cable to FlukeView Forms on a PC |
| Safety rating | CAT IV 600V / CAT III 1000V | CAT IV 600V / CAT III 1000V |
| Battery | 4 × AA; 1000 h, 1000+ insulation tests | 6 × AA; 100 h min, 200 h logging |
| Weight | 550 g (Amazon lists 1645 g) | 871 g |
| Warranty | 3 years | Lifetime limited |
Specs checked against manufacturer documentation and official Amazon listings. Desk research, not bench testing. How we research.
Key differences
- →Only the 1587 FC can stress insulation with a test voltage (50 to 1000 V) and report megohms and gigohms; the 287 has no insulation function.
- →The 287 records unattended in its own memory with a real-time clock and graphs the trend on screen; the 1587 FC sends its readings and PI/DAR graphs to the Fluke Connect app instead.
- →Current is lopsided: the 287 covers 0.01 µA resolution through 10 A, while the 1587 FC stops at 400 mA with no 10 A jack.
- →The 287 resolves finer: 50,000 counts and ±(0.025% + 2) DC volts against 6,000 counts and ±(0.09% + 2).
- →The 1587 FC has a low-pass filter for drive outputs; the 287 does not (Fluke reserves that for the 289).
- →Safety category is identical: both are CAT IV 600V / CAT III 1000V.
Power on or power off: where each meter enters a diagnosis
Most electrical diagnoses have two halves. While equipment is running you collect symptoms: a voltage that sags when a compressor starts, a current that creeps up over a shift, a control signal that drops out once an hour. After you shut it down and lock it out, you confirm a cause: a winding that has absorbed moisture, a cable whose jacket has cracked, a terminal that has tracked to ground. The 287 is designed for the first half. The 1587 FC is designed for the second.
01
Record supply
287 logs volts at the starter for a shift
02
Check load
287 reads current in series to 10 A
03
Isolate
Lock out, tag out, verify dead
04
Insulation test
1587 FC at 500 or 1000 V
05
Trend it
1587 FC PI/DAR saved in the app
That split explains almost every spec difference below. An insulation tester must hold steady test voltage into a cable and then discharge it safely, so the 1587 FC spends its design budget there and keeps the meter side to 6,000 counts and milliamps. A logging meter must sit on a live panel for a long time and capture what happens, so the 287 spends its budget on a large graphic screen, deep memory, six AA cells and a wide current range. If your work regularly includes both halves, the honest answer is that you will eventually own both kinds of instrument.
The numbers side by side
Bars use a logarithmic scale: each step is ten times the last.
Bars use a logarithmic scale: each step is ten times the last.
Bars use a logarithmic scale: each step is ten times the last.
The resistance chart needs a caution. The 287's 500 MΩ range can look like an insulation reading, but it comes from the ordinary ohms circuit, which drives only a small voltage through the part. A winding with damp or contaminated insulation can look fine at that level and still break down when a few hundred volts are applied, which is the condition a motor sees in service. That is the gap the 1587 FC's 250, 500 and 1000 V test positions close. Fluke publishes the 287's high-ohm range, not a test voltage for it, so treat it as a continuity-class check, not proof of insulation.
Current measurement shapes the toolkit
On the 287 you can put the meter in series with a load up to 10 A, read a 4–20 mA loop on the 50 mA range at 0.001 mA steps, or drop to the 500 µA range for a standby drain at 0.01 µA. Fluke publishes the burden on that microamp range as 102 µV per µA, so you can work out how much the meter itself disturbs a low-voltage circuit. With logging switched on, the same current ranges can record a compressor's draw across a whole cycle.
The 1587 FC offers just two current ranges, 60 mA and 400 mA, protected by a 0.44 A fuse. That covers control circuits and sensor loops, not motor current. Kits that bundle the 1587 FC with Fluke's i400 current clamp are separate Amazon listings; the one we link is the bare meter. If running current is part of most of your calls, pair the 1587 FC with a clamp meter (our clamp meter buying guide covers the choice) or look at a 10 A meter.
Two kinds of record keeping
Both meters let you keep evidence, but the evidence looks different. The 287 writes interval and event records into its own memory, stamped by a real-time clock, and draws them as a TrendCapture graph you can scroll and zoom on the meter. Fluke's manual sets the ceiling at 10,000 sample intervals, with event records sharing a 15,000 total; Fluke's product page words it two ways ("up to 10,000 readings" and "up to 15,000 recorded events"), which matches the manual's split between intervals and events. Full records leave the meter over an IR cable into FlukeView Forms on a PC.
The 1587 FC keeps its history in the Fluke Connect app over a 2.4 GHz radio. What it stores is less about minute-by-minute behavior and more about asset condition: a 1-minute insulation value, a PI or DAR ratio with its TrendIt graph, and the same test repeated next quarter with temperature compensation so a cold morning and a hot afternoon can be compared fairly. That is maintenance-history data. For what PI and DAR mean and how to read them, see Fluke 1587 FC vs Fluke 87V; for the 287's event records on an intermittent fault, see Fluke 287 vs Fluke 87V.
A useful way to decide
Live diagnostics on drives and electronics
One result surprises people. On a variable-frequency drive output, the insulation meter is the one with the better tool: a low-pass filter that blocks the high-frequency switching so the voltmeter shows the fundamental the motor responds to. Fluke's 287/289 manual lists that filter as "Model 289 only," so the 287 has none, and neither has LoZ. If you troubleshoot drive-fed motors and also want logging, the Fluke 289 vs Fluke 287 page explains what the extra money buys.
On control boards and instrumentation, the 287 pulls well ahead: 0.01 Ω steps on its 500 Ω range, capacitance from 1 nF to 100 mF, duty cycle and frequency to 999.99 kHz, and a 250 µs peak capture for brief spikes. The 1587 FC covers capacitance to 9,999 µF and frequency to 99.99 kHz, which handles motor-run capacitors and line frequency but not much finer electronics work. Temperature favors the 1587 FC in one way: Fluke includes a K-type thermocouple, while our sources don't state that the 287 ships with one.
Which should you buy?
| Diagnostic task | Better fit | Why |
|---|---|---|
| Motor that trips its overload after rewinding | Fluke 1587 FC | Insulation test to 1000 V, PI/DAR |
| Cable that may have been damaged by water | Fluke 1587 FC | Megohm readings at service-like voltage |
| Voltage sag that appears once a night | Fluke 287 | Time-stamped log, on-screen trend |
| Load current on a 120 V branch device | Fluke 287 | 10 A input; 1587 FC stops at 400 mA |
| Standby drain on a control board | Fluke 287 | 0.01 µA resolution |
| Voltage at a VFD output terminal | Fluke 1587 FC | Low-pass filter; 287 has none |
| Quarterly insulation checks on the same assets | Fluke 1587 FC | App history with temperature compensation |
| One meter for a mixed plant and bench job | Depends | Neither covers the other's specialty |
If insulation testing is the main reason you are shopping and you only need 500 V and 1000 V, the Fluke 1577 vs Fluke 1587 FC comparison covers the simpler model. If you work outdoors or in wet plants, read Fluke 1587 FC vs Fluke 87V MAX, since the 1587 FC is only IP40. For a broader list of meters by trade, see the best multimeters for electricians and our guide to checking a motor winding for a short.
Safety: insulation tests put high voltage on the circuit
Choose the Fluke 1587 FC if…
- ✓Your repairs end with the question "is this winding or cable still insulated?"
- ✓You want PI and DAR results, with temperature compensation, stored in an app
- ✓You troubleshoot VFD-fed motors and need a low-pass filter on AC volts
Choose the Fluke 287 if…
- ✓You chase faults that come and go, and need a time-stamped record of them
- ✓You measure load current in series up to 10 A, or sleep current in microamps
- ✓You want 50,000-count resolution and frequency readings to 999.99 kHz
The bottom line
Buy the Fluke 1587 FC if your diagnoses end at the insulation question, especially on motors, cables and drive-fed equipment; its 50 to 1000 V tests, PI/DAR and low-pass filter suit maintenance electricians. Buy the Fluke 287 if your diagnoses depend on watching a live circuit over time, measuring real load or microamp current, or resolving small changes at 50,000 counts. They overlap only in basic volts and ohms, so for many plants the right answer is one of each.
Frequently asked questions
Can the Fluke 287 test insulation resistance?+
No. The 287 has no insulation test function. Its 500 MΩ resistance range uses the ordinary ohms circuit and Fluke doesn't publish a test voltage for it, so it can't show how insulation behaves under the hundreds of volts it sees in service. For that you need an insulation tester such as the 1587 FC, which applies 50 to 1000 V.
Can the Fluke 1587 FC measure motor running current?+
Not directly in most cases. Its current inputs have 60 mA and 400 mA ranges only, with a 0.44 A fuse and no 10 A jack. That suits control circuits and sensor loops. For motor current, use a clamp meter or a kit that bundles the 1587 FC with Fluke's i400 clamp, sold as a separate Amazon listing; the one we link is the bare meter.
Which is more accurate, the Fluke 1587 FC or the 287?+
The 287, on Fluke's published specs. Its best DC volts accuracy is ±(0.025% + 2) on a 50,000-count display, against ±(0.09% + 2) on 6,000 counts for the 1587 FC. On AC volts the 287 lists ±(0.3% + 25) at 45 to 65 Hz, while the 1587 FC lists ±(1% + 3) at 50 to 60 Hz.
Does the Fluke 287 work with the Fluke Connect app?+
Not according to our sources. The 287 transfers its records over an IR optical cable to FlukeView Forms software on a PC, and Fluke doesn't list a wireless link. The 1587 FC is the Fluke Connect model of the two: it sends readings, insulation results and PI/DAR graphs to a phone or tablet over a 2.4 GHz radio.
Does the Fluke 287 have a low-pass filter for VFDs?+
No. Fluke's 287/289 manual marks the low-pass filter, LoZ and the 50 Ω range as Model 289 only. The 1587 FC does have a low-pass filter, which steadies voltage readings on drive outputs. If you need both logging and a filter in one meter, the Fluke 289 is the 280 Series model that has it.
Are the Fluke 1587 FC and 287 safe for the same electrical panels?+
Yes. Fluke rates both at CAT IV 600V and CAT III 1000V, so the measurement category is identical. One listing detail to note: the 287's Amazon page uses "Category I/II" wording that conflicts with Fluke's rating, and we follow Fluke. Always check that your test leads carry the same or higher rating.
Related