COMPARISON · MULTIMETERS

Fluke 117 vs Milwaukee 2235-20 Clamp Meter

The Fluke 117 is the better single meter for voltage, resistance and fault-finding; the Milwaukee 2235-20 is the better tool for current. Both are True RMS, CAT III 600V and read AC and DC volts to 600 V plus resistance and continuity. The difference is current: the 117 measures it only in series and tops out at 10 A, while the 2235-20 clamps around a conductor and reads up to 400 A AC without opening the circuit. If you measure load current regularly, you'll want both.

By the OhmSavvy Research Team ·

Disclosure: OhmSavvy earns a commission from qualifying Amazon purchases made through these links, at no extra cost to you. How we're funded.

Fluke 117 electrician's True RMS multimeter, front view
Best OverallHands-on Tested

Fluke 117

4.8★★★★★

The meter working electricians actually buy with their own money, not just the one brands push.

Milwaukee 2235-20 400 A True RMS clamp meter, front view
Best Clamp Meter

Milwaukee 2235-20

4.6★★★★★

Skip the test leads entirely for current readings — clamp it on and read.

Specs side by side

Fluke 117Milwaukee 2235-20
Rating4.8★★★★★4.6★★★★★
AccuracyTrue RMSTrue RMS
Safety ratingCAT III 600VCAT III 600V
Auto-ranging YesNot stated by Milwaukee
Best forElectricians, serious hobbyistsQuick current checks without disconnecting wiring
TypeHandheld digital multimeterClamp meter with test leads
AC current6 A and 10 A in series (20 A for 30 s max)To 400 A AC through the jaw
DC current6 A and 10 A in series No
Jaw openingn/a1.0 in
Volts600 V AC/DC600 V AC/DC
Resistance / continuityTo 40 MΩ / beeperYes / yes (ranges not stated on product page)
Capacitance / frequencyTo 9,999 µF / to 50 kHzNot stated
Non-contact voltageVoltAlertNot stated
LoZ inputYes, AutoVoltNot stated
LightBacklit displayBacklit display + LED work light
BatteryOne 9VTwo AAA
Warranty3 yearsNot stated on product page

Specs checked against manufacturer documentation and official Amazon listings. Fluke 117 is hands-on tested by OhmSavvy; the Milwaukee 2235-20 assessment is desk research. How we research.

Key differences

  • →Current method: the 2235-20 reads AC current by clamping one conductor; the 117 has to be wired into the circuit in series.
  • →Current range: the clamp reaches 400 A AC. The 117 stops at 10 A continuous (20 A for 30 seconds), so a 15 A or 20 A branch circuit under full load is beyond it.
  • →DC current: only the 117 measures it. Milwaukee rates the 2235-20 for AC current only.
  • →Both read AC and DC volts to 600 V, resistance and continuity, and both are True RMS and CAT III 600V.
  • →The 117 adds VoltAlert non-contact detection, a LoZ AutoVolt position, capacitance and frequency; Milwaukee doesn't list these for the clamp.
  • →The 2235-20 adds an LED work light and runs on two AAA cells; the 117 uses one 9V battery.

At a glance

Shared core

True RMS, CAT III 600V, 600 V AC/DC, resistance and continuity.

Clamp's job

AC load current to 400 A without touching or opening the circuit.

117's job

Fault-finding: NCV, LoZ for ghost voltage, capacitance and frequency.

Current ceiling

117: 10 A in series. 2235-20: 400 A AC around one conductor.

DC amps

117 only. The 2235-20 does not measure DC current.

Verdict

One tool for wiring work: 117. Regular load checks: add the clamp.

The Fluke 117 is one of the meters the owner has bought and used, hence its Hands-on Tested badge; the Milwaukee assessment is desk research against the maker's published specs. Full single-tool write-ups: the Fluke 117 review and the Milwaukee 2235-20 review.

Fluke 117 vs Milwaukee 2235-20 spec by spec

On voltage the two are the same tool: 600 V AC and DC, True RMS, CAT III 600V. Everything that separates them is about current, plus the electrician extras Fluke built into the 117.

Fluke 117 (in series)
10 A
Fluke 117, 30 s max
20 A
Milwaukee 2235-20
400 A

Bars use a logarithmic scale: each step is ten times the last.

Highest continuous AC current, on a log scale. The clamp reaches 40 times higher than the 117's 10 A input.
Fluke 1172235-20AC volts to 600 VDC volts to 600 VResistanceContinuityAC current, no breakCurrent above 10 ADC currentCapacitancenot statedFrequencynot statedNon-contact voltagenot statedLoZ ghost-voltage checknot statedLED work light
What each tool measures, per Fluke and Milwaukee. Filled dot = listed; "not stated" = not on Milwaukee's product page.

The 10 A ceiling matters more than it sounds. A 120 V branch circuit on a 20 A breaker can legitimately carry up to 16 A of continuous load under the common 80% rule, and a hair dryer or space heater at 1,500 W draws 1,500 ÷ 120 = 12.5 A. Neither can be read on the 117 except for a few seconds, and wiring a meter in series means switching off, opening a connection and exposing terminals. The clamp reads all of them through the jaw with the panel cover off and nothing disconnected.

How each tool measures current

A multimeter measures current by making the current flow through an internal shunt, so the circuit has to be broken and the meter inserted. A clamp meter's jaw is the core of a current transformer: alternating current in the conductor creates an alternating magnetic field, and the jaw converts that into a reading. That is also why an AC-only clamp like the 2235-20 can't see DC, which produces a steady field that a transformer-style jaw can't sense.

Multimeter: in seriesAloadcircuit opened,current runs throughthe meter (10 A max)Fluke 117: 6 A / 10 A rangesClamp: around one wireloadjaw senses the magneticfield; circuit stays closedMilwaukee 2235-20: to 400 A AC
Left: the 117 must become part of the circuit. Right: the 2235-20 reads the field around one conductor.
  1. 01

    Open the panel

    Dead-front off, PPE on

  2. 02

    Pick one conductor

    Hot or neutral, not both

  3. 03

    Close the jaw

    Conductor centered

  4. 04

    Read amps

    Compare with breaker rating

Clamp one wire, not the whole cable

Around a complete cord or cable, the outgoing current on the hot and the returning current on the neutral create equal and opposite fields, so a clamp reads close to zero even under full load. Separate a single conductor in the panel, or use a line splitter for plug-in loads. A reading that is suspiciously low is usually a clamp around two conductors, not a light load.

Fluke 117 vs Milwaukee 2235-20: which should you buy?

JobBetter toolWhy
Is this receptacle live?Fluke 117VoltAlert first, then the leads; both read 600 V AC
Phantom voltage on an abandoned runFluke 117LoZ AutoVolt drains capacitive ghost voltage
Why does this breaker keep tripping?Milwaukee 2235-20Reads the actual load current on the circuit
Motor or compressor amp drawMilwaukee 2235-20Compares running amps with the nameplate without disconnecting
Run capacitor checkFluke 117Capacitance to 9,999 µF; not stated for the clamp
Car or solar DC currentFluke 117 (to 10 A)The 2235-20 can't read DC amps
Continuity on a cable runEitherBoth list resistance and continuity
One tool on a tight budgetFluke 117Covers more everyday electrical jobs

For clamp technique, see our guide to measuring AC current with a clamp meter, and the clamp meter buying guide if you need DC amps too. Tripping breakers are covered step by step in why a circuit breaker keeps tripping.

Safety: the 10 A jack is the risky one

Measuring current with the 117 means switching to the A jack and putting the meter in series. Leave the leads in that jack and touch a live 120 V or 240 V circuit, and you create a short through the meter's fuse. Turn the circuit off before you open it, and move the red lead back to the V jack as soon as you finish. With the clamp, nothing is disconnected, but you still work inside a live panel, so wear insulated gloves and eye protection, keep fingers behind the jaw's tactile barrier, and leave service-entrance measurements to a licensed electrician with CAT IV equipment.

Choose the Fluke 117 if…

  • ✓Most of your work is voltage checks, continuity and tracing wiring faults
  • ✓You want VoltAlert non-contact detection and a LoZ position for ghost voltage in one meter
  • ✓You need capacitance, frequency or small DC currents, which Milwaukee doesn't list for the clamp

Choose the Milwaukee 2235-20 if…

  • ✓You check motor, compressor or feeder current and don't want to break the circuit
  • ✓Your loads draw more than 10 A, beyond what the 117 can read
  • ✓You want a backlit display and a built-in LED work light for dark panels

The bottom line

If you can own only one, the Fluke 117 covers more everyday electrical work: voltage, continuity, resistance, capacitance, NCV and a LoZ check. Add the Milwaukee 2235-20 when measuring load current becomes part of the job, because it reads to 400 A AC without opening anything. The two complement each other rather than compete.

Frequently asked questions

Can the Milwaukee 2235-20 measure resistance and continuity?+

Yes. Milwaukee ships it with a set of test leads and lists resistance and continuity alongside AC and DC volts to 600 V. What it doesn't list on the product page are capacitance, frequency, non-contact voltage or a LoZ input, which the Fluke 117 has. For basic continuity checks on a cable run, either tool works.

Can the Fluke 117 measure amps on a 20 A circuit?+

Only briefly. Its current input is rated 10 A continuous, with 20 A allowed for 30 seconds at most, and it must be wired in series. A 20 A branch circuit near full load exceeds that. A clamp meter such as the Milwaukee 2235-20 reads the same current around one conductor with nothing disconnected.

Does the Milwaukee 2235-20 measure DC current?+

No. It is rated for AC current up to 400 A. DC current produces a steady magnetic field that an AC-only clamp jaw can't sense; reading DC amps through a jaw requires a Hall-effect clamp. For DC amps up to 10 A in series, the Fluke 117 can do it.

Why does my clamp meter read zero on an extension cord?+

Because the jaw is around both the hot and neutral. Their currents flow in opposite directions, so the magnetic fields cancel and the meter sees almost nothing. Clamp a single conductor in the panel, or plug the load into a line splitter that separates the hot and neutral into a loop you can clamp.

Do electricians need both a multimeter and a clamp meter?+

Most carry both. A multimeter like the Fluke 117 handles the volts, continuity and fault-finding that fill most of a service call, with NCV and LoZ for safer, faster checks. A clamp like the 2235-20 answers the load question, how many amps a circuit or motor is drawing, without opening the circuit. Neither fully replaces the other.